Permit Number: T08CM01098
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01098
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2008 TERRY STEVENS ZONING REVIEW Approved
04/07/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the ventilation of the restrooms complies with the requirements of Section 403.3, IMC 2006.
04/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Did not see new AC unit on Mechanical plans. Please coordinate with Mechanical.
2. New Water Heater is 13.75A and 2 KW per Sheet MP.1. At 13.75A this would be 2860W. Clarify power requirements.
3. Electrical provides 120V power for New Water Heater. Plumbing specifies 208V. Clarify and coordinate.
4. Please note that series rating is specified for both Panels A and B. Since Panel B appears to be existing, to remain, and is not being relocated, I would suggest that its existing rating is already in compliance. This may not be the case of course, but if the intent is to leave Panel B alone in the present scope of work this specification has the potential to introduce unnecessary cost and delay.
04/07/2008 ROBERT SHERRY WATER REVIEW Approved
04/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/07/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/07/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the waste and vent diagram with respect to the "point of use water dispenser".
2. Provide upper terminal cleanouts at the water closets and at the mop sink.
3. Provide a vacuum relief valve for the water heater. Reference Section 608.7, UPC 2006.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
04/07/2008 MARTIN BROWN FIRE REVIEW Approved
04/07/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/08/2008 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2008 DELMA ROBEY APPROVAL SHELF Completed
04/08/2008 DELMA ROBEY OUT TO CUSTOMER Completed
04/08/2008 DELMA ROBEY REJECT SHELF Completed