Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01098
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/07/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the ventilation of the restrooms complies with the requirements of Section 403.3, IMC 2006. |
| 04/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Did not see new AC unit on Mechanical plans. Please coordinate with Mechanical. 2. New Water Heater is 13.75A and 2 KW per Sheet MP.1. At 13.75A this would be 2860W. Clarify power requirements. 3. Electrical provides 120V power for New Water Heater. Plumbing specifies 208V. Clarify and coordinate. 4. Please note that series rating is specified for both Panels A and B. Since Panel B appears to be existing, to remain, and is not being relocated, I would suggest that its existing rating is already in compliance. This may not be the case of course, but if the intent is to leave Panel B alone in the present scope of work this specification has the potential to introduce unnecessary cost and delay. |
| 04/07/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/07/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/07/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/07/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste and vent diagram with respect to the "point of use water dispenser". 2. Provide upper terminal cleanouts at the water closets and at the mop sink. 3. Provide a vacuum relief valve for the water heater. Reference Section 608.7, UPC 2006. 4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 04/07/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/07/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/08/2008 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/08/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 04/08/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/08/2008 | DELMA ROBEY | REJECT SHELF | Completed |