Permit Number: T08CM01096
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01096
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
04/07/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/07/2008 ROBERT SHERRY WATER REVIEW Approved
04/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/07/2008 GERRY KOZIOL WWM REVIEW Approved
04/07/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference: Section 402.1, UPC 2003, as amended by the State of Arizona.
2. Show how the temperature of the hot water supply to the public lavatories is controlled to a maximum temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
04/07/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/07/2008 MARTIN BROWN FIRE REVIEW Approved
05/05/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review