Review Details: REVISION - - 3RD

Permit Number - T08CM01061
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3440 E BRITTANIA #100
T I Office
T08cm01061-Revision

Regarding your response to the previous comments , there does not appear to be compliance with NEC 2005 230-2 nor 230-72. Your response refers to possible special permission being issued for the prior 3 services to one location, which I am not aware of, however to obtain special permission again, would require you to go through an appeal to the Building Official. The form for this may be obtained thur our office. Once filled and submitted to the building Official he approves or disapproves.
The question of the additional 4th service was shown to our Electrical Plans Examiner prior to making the call in order to verify my call .


Ray T Majuta
Elect Plan Check
DSD City of Tucson
520-8374988
8/12/08