Permit Number: T08CM01061
Parcel: 14029003H

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T08CM01061
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3440 E Britannia #100
T08CM01061
Electrical Revision

The plans for this revision have been denied for the following items:

1. The drawings show a fourth new service being added to the building, please clarify the following,

How does this new service comply with Section 230-2 of the 2005 NEC, which requires only one service to serve each structure unless permitted by one of the items listed under 230-2 A thur D, or 230-40 exception 2 ?
Is the occupancy for one tenant ?
How does the installation comply with Section 230-72 of the 2005 NEC requiring grouping of disconnects ? Do you constitute being in the same room grouped ? What are the demensions of the electrical room ?


Ray T Majuta
DSD City of Tucson
Electrical Plan Check
520-837/4988
8/04/08

Final Status