Review Details: REVISION - - 2ND
Permit Number - T08CM01061
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 3440 E Britannia #100 T08CM01061 Electrical Revision The plans for this revision have been denied for the following items: 1. The drawings show a fourth new service being added to the building, please clarify the following, How does this new service comply with Section 230-2 of the 2005 NEC, which requires only one service to serve each structure unless permitted by one of the items listed under 230-2 A thur D, or 230-40 exception 2 ? Is the occupancy for one tenant ? How does the installation comply with Section 230-72 of the 2005 NEC requiring grouping of disconnects ? Do you constitute being in the same room grouped ? What are the demensions of the electrical room ? Ray T Majuta DSD City of Tucson Electrical Plan Check 520-837/4988 8/04/08 |