Permit Number: T08CM01061
Parcel: 14029003H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01061
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. PREVIOUS COMMENT 6 CONCERNING PAPER DISPENSER LOCATION SHOULD BE 7" TO 9" PER FIG. 604.7 OF THE ICC/ANSI A117.1.
05/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the listing material for the DI system being provided by the owner. Reference: Section 301.1, UPC 2006.
05/20/2008 ROBERT SHERRY WATER REVIEW Approved
05/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2008 DELMA ROBEY APPROVAL SHELF Completed
05/20/2008 DELMA ROBEY OUT TO CUSTOMER Completed
05/20/2008 DELMA ROBEY REJECT SHELF Completed