Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01061
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/03/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/04/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; CODE REVIEW: LISTED 1 REQUIRED EXIT PER TABLE 1019.1; IT DOES REQUIRE 2. VERIFY. 2. SHEET A1.0; CODE REVIEW: LISTED 4 PROVIDED EXITS; ONLY 3 SHOWN. VERIFY. 3. SHEET A1.0; EXIT KEY PLAN: NORTHERNMOST EXITWAY GOES THROUGH A STORAGE ROOM. THIS IS NOT ALLOWED PER IBC 1014.2.2. A DEAD END IS THEREFORE CREATED, WHICH IS NOT ALLOWED PER IBC 1017.3. 4. SHEET A1.0; FLOOR PLAN: VERIFY CLEARANCES AT DRINKING FOUNTAIN MEET ICC 117.1 SECTION 602.2. PROVIDE ENLARGED, DIMENSIONED PLAN. 5. SHEET A1.0; FLOOR PLAN: PROVIDE ENLARGED, DIMENSIONED PLANS OF RESTROOMS #134, 135, 120, AND 122, INCLUDING ALL ADA CRITICAL ISSUES PER 2006 IBC AND 2003 ICC/ANSI A117.1. 6. SHEET A3.0; INTERIOR ELEVATIONS: RELOCATE PAPER DISPENSER PER ICC/ANSI A117.1, FIG. 604.7. 7. SHEET M2.2; ROOF PLAN: VERIFY NEW HEAT PUMPS/EXHAUST FANS ARE SIMILAR (WITHIN 20%) TO WEIGHT OF EXISTING UNITS. IF NOT, REQUIRE CALCULATIONS FOR ADEQUACY OF EXISTING ROOF STRUCTURE. NOTE ON DRAWINGS. |
04/07/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/15/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | THE FOLLOWING ELECTRICAL ITEMS REQUIRE REVIEW 1. SHEET E2.0, INDICATES THAT A RELOCATED 75 KVA TRANSFORMER CONCERNING PANELS LC AND PE IS TO BE LOCATED ABOVE A CORRIDOR CEILING, HOW WILL THIS COMPLY WITH NEC 2005, 450-13.B, WHICH ALLOWS TRANSFORMERS BELOW 50KVA ABOVE CEILINGS ? 2. THE CONDUCTORS FROM EXISTING 1600 AMP CT TO NEW 800 AMP CT TO BE DIFFERENT. ONE SHEET SHOWS 500MCM'S OTHER SHOWS 600MCM'S. 3. CONNOT LOCATE MAINTENANCE RECEPTACLES FOR NEW HP UNITS ON ROOF, SHEET E2.1 RAY MAJUTA ELECTRICAL PLAN CHECK, DSD 4/16/08, 837-4988 |
04/21/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Indicate if this building is provided with a reduced pressure backflow assembly at the water service entrance. Reference: Section 103.2.3, UPC 2006. |
04/21/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 2. Provide the listing material for the DI system being provided by the owner. Reference: Section 301.1, UPC 2006. |
04/21/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the status of HP-1; is it new or existing? The roof curb note on the mechanical roof plan (1/M2.2) appears to indicate4 a new unit but the heat pump schedule implies an existing unit. Reference: Section 106.3.1, IMC 2006. 2. Show that there is a minimum separation of the exhaust fans from the outside air inlets of the heat pumps that complies with Section 401.4.1, IMC 2006. 3. Clarify the nature of the exhaust from room 158 (Electric Lab). Reference: Section 106.3.1, IMC 2006. |
04/30/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/05/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
05/05/2008 | SHANAE POWELL | REJECT SHELF | Completed |