Permit Number: T08CM01054
Parcel: 12710084B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01054
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2008 STEVE SHIELDS ZONING REVIEW Approved
04/02/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01054 4/2/08

1. Provide disconnecting means approproate for hard-wired Insta-Hots.
2. Show windows counted at 200VA/LF per NEC 220.43 (B).
3. Account for continuous load and largest motor on panel schedule.
4. Specify conductor size for Insta-Hots.
5. Show that the electrical service is not being overloaded.
04/02/2008 ROBERT SHERRY WATER REVIEW Approved
04/02/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/02/2008 JASON GREEN ENGINEERING REVIEW Approved
04/02/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/02/2008 MARTIN BROWN FIRE REVIEW Approved
04/15/2008 CPIERCE1 WWM REVIEW Needs Review
04/15/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review