Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01054
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/02/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01054 4/2/08 1. Provide disconnecting means approproate for hard-wired Insta-Hots. 2. Show windows counted at 200VA/LF per NEC 220.43 (B). 3. Account for continuous load and largest motor on panel schedule. 4. Specify conductor size for Insta-Hots. 5. Show that the electrical service is not being overloaded. |
| 04/02/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/02/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/02/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/02/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/15/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 04/15/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |