Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01046
Parcel: 117042890

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01046
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/02/2008 MARTIN BROWN FIRE REVIEW Approved
04/02/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/08/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. IDENTIFY PROPERLY ALL THREE SPACES AND ASSOCIATED SUITE NUMBERS
2. REVISE BUILDING DATA PER INDIVIDUAL SUITE NUMBERS
3. NEED FURTHER INFORMATION AND DETAILING FOR MOUNTING OF HVAC UNITS. PROVIDE DETAIL SHOWING CONNECTION TO EXISTING RIDGE BEAM AND SLOPED ROOF JOISTS
4. PROVIDE DETAILING AND STRUCTURAL CALCULATIONS FOR INTERIOR PARTITIONING
04/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide mechanical plans (see details 1/M1.1 and 2/M1.1) with a legible background. Reference: Section 106.3.1, IMC 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
04/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/18/2008 ROBERT SHERRY WATER REVIEW Approved
04/29/2008 GERRY KOZIOL WWM REVIEW Denied 1:Sears Financial corp
2:needs to show location/method of connection to public sewer
3:property does not front public sewer-needs wastewater 8th floor review of location/method of connection to public sewer
4:needs wastewater 8th floor review of easement/joint use sewer agreements if applicable
05/05/2008 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2008 VFLORES1 OUT TO CUSTOMER Completed
05/09/2008 SUE REEVES REJECT SHELF Completed