Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM01044
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2008 PETER MCLAUGHLIN ZONING REVIEW Denied 1) A 5-foot pedestrian refuge area with a minimum 4-foot sidewalk is required between the PAAL and the building (adjacent to the south side of the building) per DS 3-05.2.2.B.1. Revise the plan accordingly to show the required pedestrian refuge area and sidewalk. Approval of a DSMR (Development Standard Modification Request) will be required if no sidewalk/pedestrian refuge is being provided. If a DSMR is sought and approved add a note to the plan stating the case number, date of approval, what the DSMR was approved for and any conditions imposed.

2) Pedestrian circulation must be provided to the building and at least one sidewalk must be provided from the street on which the project has frontage. Sidewalks must connect all areas of the development. DS 2-08.4.1 See comment 1 regarding DSMR approval to waive the requirement for continuous on-site pedestrian circulation.

3. The last approved site plan submitted does not show the additions and covered storage areas. Provide permitting information for these additions. If they have not yet been permitted, they must be included as part of this application.

4. Add a note to the site plan stating that all improvements within the future right-of-way of Flowing Wells Road shall be removed/relocated at no cost to the City of Tucson if necessary in the event future street widening improvements are made.
10/17/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1) The proposed parking lot construction requires full code compliance for the site.

2) Provide a separate landscape and irrigation plan detailing proposed landscaping, screening and irrigation per DS 2-06 and 2-07.

3) Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces or fraction thereof and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a

4) A 10-foot street landscape border with a 30-inch screen is required along Flowing Wells Road per LUC Table 3.7.2-I. Indicate required landscape border and screening on the landscape plan.

5) Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4

6) Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g

7) One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border or fraction thereof per LUC 3.7.2.4.

8) A 30" continuous screen along MS&R street frontages, except at vehicle and pedestrian access points, must be provided per LUC Table 3.7.2-I

9) The latest response comments indicate that landscaping and screening requirements will not be met. A Board of Adjustment application must be submitted and approved for relief from the above Land Use Code requirements for landscaping. If variances are approved for the above code requirements add a note stating the Board of Adjustment case number, date of approval, what variances were approved, and any condions imposed. Note that if variances are sought, the Zoning Review comments regarding pedestrian circulation can be addressed through the same Board of Adjustment process rather than submitting a separate DSMR application.
11/07/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: November 7, 2008
SUBJECT: Site plan with Parking - Demolition
TO: Intertech
LOCATION: 2902 N Flowing Wells, T14S, R14E, Section 19, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM01044 (Third Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Include a response letter to the comments along with the corrected copies of the site plan.

Please verify that all text on the submitted site plan is a minimum of 0.12 point font.

Recently the FINE for handicap signs has changed. Please change all handicap signs to read $532 FINE.

Site Plan:

1. Complied
2. Revise and label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Even though the future ROW goes into the existing building, please provide the information as reaquested.

Engineering Reponse: Site Visibility Triangle dimensions appear to be depicted incorrectly on site plan. This site has a transition of a PAAL to a Collector road. Near side dimension should be 265' - Far side is correctly depicted at 125'.

3. Please label all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.

Engineering Reponse: Please label the entrance to that PAAL from Flowing Wells Road. Change * indicated under dimensions for PAALs and label PAAL under dimensions.

4. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Depict and label 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along Flowing Wells Road. The curbs should be constructed at the edge of pavement and entirely on the subject property, which must also be depicted on the site plan. For exception or questions in regard to Transportation Management Guidelines please contact Jose Ortiz, Civil Engineer with the Trasportation Department. Comment acknowledged, please provide approval from the Transportation Department.

Engineering Reponse: I am unable to approve request without prior approval from the City of Tucson Transportation Department. For relief from this requirement please contact the City of Tucson Transportation Department. If the Transportation Department approves the proposed design then have them sign off the plans and send me (Bianca Ramirez, CFM - Engineering Associate) and email to bianca.ramirez@tucsonaz.gov.

5. Indicate curb returns for MS&R and call out radius on plans. Comment acknowledged, please provide approval from the Transportation Department.

Engineering Reponse: Again get approval from the City of Tucson Transportation Department for relief from this requirement.

6. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12. Comment acknowledged provide pedestrian circulation must be provided to the building and at least one sidewalk must be provided from the street on which the project has frontage. Sidewalks must connect all areas of the development. Please revise accordingly per DS 2-08.4.1

Engineering Reponse: I am unable to approve relief from requirement through response letter. Such a request requires Development Standard Modification Request (DMSR) and compliance with the Zoning requirements. See Zoning requirements.
.
7. Complied

8. DS 2-02.2.1.A.12: Revise the site plan to show the required pedestrian circulation path that is required from the poropes building to the required pedestrian circulation path located along Flowing Wells Road.

Engineering Reponse: I am unable to approve relief from requirement through response letter. Such a request requires Development Standard Modification Request (DMSR) and compliance with the Zoning requirements. See Zoning requirements.
.
9. Show the limits of the 100-year floodplain and water surface elevation(s) on the site plan per D.S. 2-02.2.1.15. Comment acknowledged - identified 100-year floodplain does not match maps. Please revise accordingly - provide note on site plan that reads: Parcel is 100% within City of Tucson identified 100-year floodplain.

Engineering Reponse: Revise note on site plan to read: Parcel is 100% within City of Tucson identified 100-year floodplain.

10. Complied

11. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof drainage.

1. Engineering Reponse: Provide drainage arrows to show the roof drainage patterns. 100% of the 10-yeat flow must be conveyed under the sidewalks including any other site drainage as well.
12. Complied

13. Complied

14. Complied

15. Information not available. Complied.

16. Complied

17. Complied

18. Complied

19. Complied

20. Complied

21. Complied

22. Complied

23. DS Sec.2-02.2.1.A.32: fully dimension trash enclosure on site plan and provide a detail with dimensions for refuse container on the site plan, the enclosure must have a minimum inside clear dimension of 10 feet by 10 feet between steel bollards that are required between the container and the enclosure's rear and sidewalk. Refer to attached detail DS Sec.6-01.0 for specifications and requirements. Comment acknowledged, provide detail of trash enclosre - see attached trash enclosure detail for example of detail. Include dimensions within detail.

Engineering Reponse: Full - code compliance required that the trash enclosure meets the minimum trash enclosure requirements. For relief from this requirement approval from the City of Tucson Environmental Department will be required. Provide approval and email from Environmental Services for approval of request.

24. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

25. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the gradebreak at the driveway, if applicable. Comment acknowledged, provide cross section refered to on the landscape plan and provide on the site plan.

Engineering Reponse: Unable to located the cross section on site plan. Please verify that it was placed on plans. If I missed please indicate where it can be found on the plans (ie sheet).

26. Complied

27. Add note: "Depress all landscaped areas 6" maximum for water harvesting". Comment acknowledged, provide note on the site plan.

Engineering Reponse: Unable to approve request from relief from requirement. Provide approval from the City of Tucson Landsape Department and have approval complete as well as email sent to me stating that request will be granted.

28. Complied

29. Complied

30. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax