Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM01037
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/02/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Tucson Water limits a 1" meter to a maximum demand of 25 GPM. Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for the water supply to the east side of this project (27.3 GPM). |
| 06/02/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/11/2008 | CPIERCE1 | APPROVAL SHELF | Completed |
| 06/11/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/11/2008 | GERARDO BONILLA | REJECT SHELF | Completed |