Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01036
Parcel: 129041820

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01036
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2008 STEVE SHIELDS ZONING REVIEW Approved
04/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006
04/01/2008 ROBERT SHERRY WATER REVIEW Approved
04/01/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied TOILETS ARE NOT ACCESSIBLE
04/08/2008 MARTIN BROWN FIRE REVIEW Approv-Cond
04/08/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/14/2008 CAGUILA1 WWM REVIEW Needs Review
04/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM01036 4/8/08

1. Ckt B-1 is an Air Handler on the panel schedule. Powers receptacle load on Electrical Plan. CORD-CONNECTED, TYPICAL FOR 1035
2. Indicate whether water heater is electrical. If so, add to panel schedule.
3. Provide fault current rating for Panel B.
4. Provide fault calculations for New Panel B.
5. On the Service load, please note that the divisor for the high phase should be 120V, not 230V.
04/14/2008 CAGUILA1 ENGINEERING REVIEW Needs Review