Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01035
Parcel: 129041820

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01035
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2008 STEVE SHIELDS ZONING REVIEW Approved
04/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006
04/01/2008 ROBERT SHERRY WATER REVIEW Approved
04/01/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. TOILETS ARE NOT ACCESSIBLE
04/01/2008 PAUL MACHADO ENGINEERING REVIEW Approved
04/01/2008 DAVE MANN FIRE REVIEW Approved
04/14/2008 CAGUILA1 WWM REVIEW Needs Review
04/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t08cm01035 4/8/08

1. Ckt 5A powers Air Handler on panel schedule. This is a receptacle on the Electrical Plan. Please clarify.
2. Demonstrate compliance with the Tucson Lighting Code for the exterior fixture. Or, if existing, please indicate so on the plans.
3. Fill in the electrical load and description on Ckt A-14. This is not a spare.
4. Keynote 4 points to what appears to be a panelboard on the interior south wall. Not a fixture.
5. Please account for 75VA/LF on panel calculations for the track lights on Ckt 3A. Reference NEC 220.43 (B).
04/14/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review