Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01035
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/01/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/01/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
04/01/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006 |
04/01/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/01/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. TOILETS ARE NOT ACCESSIBLE |
04/01/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
04/01/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
04/14/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
04/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t08cm01035 4/8/08 1. Ckt 5A powers Air Handler on panel schedule. This is a receptacle on the Electrical Plan. Please clarify. 2. Demonstrate compliance with the Tucson Lighting Code for the exterior fixture. Or, if existing, please indicate so on the plans. 3. Fill in the electrical load and description on Ckt A-14. This is not a spare. 4. Keynote 4 points to what appears to be a panelboard on the interior south wall. Not a fixture. 5. Please account for 75VA/LF on panel calculations for the track lights on Ckt 3A. Reference NEC 220.43 (B). |
04/14/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |