Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM01016
Parcel: 128140630

Address:
5232 E 18TH ST

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T08CM01016
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/21/2008 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Approved T08CM01016 8/21/08

#2 conductor has ampacity of 115A. Not sufficient for 125A load calculated for Panel B.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2008 VFLORES1 OUT TO CUSTOMER Completed