Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T08CM01016
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/21/2008 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM01016 8/21/08 #2 conductor has ampacity of 115A. Not sufficient for 125A load calculated for Panel B. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |