Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM01016
Parcel: 128140630

Address:
5232 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM01016
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2008 GERRY KOZIOL WWM REVIEW Approved
04/01/2008 DAVE MANN FIRE REVIEW Approved
04/01/2008 ROBERT SHERRY WATER REVIEW Passed
04/02/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size of the duct and the location of the intake for the outside air duct for FC-1. Reference: Sections 106.3.1 and 401.4.1, IMC 2006.
2. Provide a Type I hood over all domestic cooking appliances (i.e. range) used for commercial purposes. Reference: Section 507.2.3, IMC 2006.
04/02/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
04/02/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied PAGE G101
1. ACCESSIBLE CODE TO BE 2006 IBC, ICC 117.1, SECTION 1101.2
2. DELETE OCCUPANT LOAD CALCULATIONS SHOWING LOAD OF 20 OCCUPANTS. THIS IS NOT APPLICAPABLE. RETAIN OCCUPANT LOAD OF 10.
SHEET G201
3. CODE NOTE 3: IBC SECTION 1004 IS FOR OCCUPANT LOAD. REFERENCE IBC SECTIONS 1015 AND 1019 FOR EXITS. REDO EXIT REQUIREMENTS
4. CODE NOTE 9: REFERENCE HERE IS FOR ADAAG CURB RAMPS. REFERENCE ICC 117.1 608.2.2 FOR STANDARD SHOWER AND SEAT REQUIREMENETS
5. CODE NOTE 13: VERIFY DEAD END CORRIDOR EXCEPTION AFTER RECULATION OF NOTE 3
6. DETAIL C1/FLOOR PLAN: ADJUST CLEARANCE SPACE POSITIONING AT ACCESSIBLE SINK AS PER ICC 117.1 FIGURE 306.3
7. AT REAR (SOUTH) EXIT DOOR, STRIKE JAMB CLEARANCE DOES NOT MEET ICC 117.1 FIGURE 404.2.3.1 (B), REFERENCE YOUR DETAIL K8/G301
SHEET S101
8. DEFERRED SUBMITALS NOTE 4: ALL DEFFERED SUBMITTALS MUST HAVE BUILDING OFFICIAL APPROVAL, SUBMIT LETTER OF REQUEST TO ACTING BUILDING OFFICIAL, MR. JESSE SANDERS AND INCLUDE WITH RESUBMITTAL.
9. SPECIAL INSPECTIONS, NOTE 1: PROVIDE COMPLETED SPECIAL INFORMATION FORM WITH LISTED, APPROVED INSPECTION ENGINEER
SHEET A101
10. PROVIDE A 4' HIGH WAINSCOATING IN ALL TOILET ROOMS AS PER 2006 IBC SECTION 1210.2
11. SHEET S201; FOUNDATION PLAN NOTE #3: REFERENCE TO TYPICAL DETAILS: WHERE ARE THOSE? PROVIDE.
12. SHEET S201; FOUNDATION PLAN NOTES #6 AND #7: PROVIDE TYPICAL CONTROL JOINT/EXPANSION JOINT DETAILS.
13. SHEET S201: INDICATE LOCATION OF ALL SHEARWALL HOLDOWNS.
14. SHEET A501; DETAIL F11: CLARIFY #4 VERTICALS AT COLUMN (LENGTH OF BENT LEG/VERTICAL LENGTH). TIE REINFORCING IS INDICATED, BUT NOT CALLED OUT. VERIFY.
15. SHEET A501; DETAIL L7: REFERENCE FOR DEPTH OF FOOTING SAYS 'SEE STRUCTURAL'. VERIFY WHERE ON STRUCTURAL.
16. SHEET S201; FOUNDATION PLAN: SECTION J11/A501 CUT ON EAST WALL SHOULD BE L7/A501. VERIFY.
17. SHEET A501; DETAIL M15: REFERENCE FOR WIDTH OF FOOTING SAYS 'SEE FOUNDATION PLAN'. VERIFY WHERE ON PLAN.
18. SHEET S201; FOUNDATION PLAN NOTE #1: PROVIDE SLAB REINFORCING.
19. SHEET S201; FOUNDATION PLAN: SW2 ON EAST AND WEST WALLS (4 LOCATIONS) NEED TO BE SPECIFICALLY LOCATED.
20. SHEET S301; KEYNOTES #5: PROVIDE SPLICE DETAIL.
21. SHEET A 502; DETAIL D7/A7/D4/D11/G15/L15: PROVIDE CONNECTION OF 2 X BLOCKING/RIM BOARD TO TRUSS/JOIST/OUTRIGGER.
22. SHEET S301; CALCULATIONS SHEET 4: B6 ON THE DRAWING DOES NOT AGREE WITH THE CALCULATIONS. VERIFY.
04/17/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments for T08CM01016, 5232 E 18th St,
the electrical portion of the plan has been rejected for the following items,

1. Sheet E101 Electrical specifications to reflect current code used---IRC 2006, and 2005 C of T Outdoor Lighting Ord.

2. Panel A circuit 6,8 shows a 100 amp circuit breaker to Panel B, with 150 amp conductors terminating at Panel B.
Panel B is calculated at 107.7 amps. This cituation needs to be corrected. Perhaps if a washer circuit can be relocated to Panel A lowering load, and conductors reduced to 3#3's cu #8 cu grd then the 100 amp breaker would allow the #3's to terminate. Otherwise the #1 conductors will not terminate on the 100 amp breaker. Non-the less the correction must be made in an acceptable manner.
Correct and resubmit.

Ray T Majuta
DSD Electrical Plan Ck
Electrical Dept,
4/18/08
04/21/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
04/23/2008 SHANAE POWELL REJECT SHELF Completed