Permit Number: T08CM01011
Parcel: 130060030

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM01011
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
2. Provide a cleanout for the building sewer down stream of the new backwater valve. Reference: Section 719.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
03/04/2009 SUE REEVES REJECT SHELF Completed