Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01009
Parcel: 130060030

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM01009
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide revisions to the roof framing drawing to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit in the new location. Reference: Section 302.1, IMC 2006
02/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the building sewer down stream of the new backwater valve. Reference: Section 719.1, UPC 2006.
2. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
02/23/2009 SUE REEVES REJECT SHELF Completed