Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM01009
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide revisions to the roof framing drawing to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit in the new location. Reference: Section 302.1, IMC 2006 |
02/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a cleanout for the building sewer down stream of the new backwater valve. Reference: Section 719.1, UPC 2006. 2. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/23/2009 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
02/23/2009 | SUE REEVES | REJECT SHELF | Completed |