Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00976
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/26/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/26/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/26/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00986 3/26/08 1. Count 75VA/LF for track lighting. 2. Provide panel and circuit number for lighting circuit for existing women's room. 3. Provide Plumbing plans for Water Heater. 4. IECC calculations indicate this is a Medical Office. I'm told this is a Law Office. Please clarify. |
| 03/26/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/26/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/26/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 03/26/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/01/2008 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
| 04/01/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information regarding the installation of the new water heater. |
| 04/01/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |