Permit Number: T08CM00974
Parcel: 11108127A

Address:
2513 N RICHEY BL

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00974
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2008 GERRY KOZIOL WWM REVIEW Denied needs 5th floor credit evaluation
09/30/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM000974

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" All code references to the International Residential Code shall be changed from 2003 to 2006. Change references on sheet 2, 3 & 5.

FOUNDATION PLANS:

1. Provide a landing or floor surface at all exterior doors. A landing must be at least as wide as the door it serves and 36" in the direction of travel, R311.4.3.

FLOOR PLANS:

1. Show the location of a minimum 22" x 30" attic access. Attic access is required if the space exceeds 30 SQ FT with a minimum of 30" of headroom, and shall be located in a hallway or readily accessible space, R807.1.

STRUCTURAL PLANS:

1. Show the location of the HVAC load on the roof framing plan and provide additional load carrying capacity, R301.1.
2. Provide ridge beams sized for supporting roof live and dead loads, R301.1. The 2-2x6 beam is undersized for spans exceeding 5'9".
3. Provide rafter sizes and spacing in compliance with Table R802.5.1.
4. Provide ceiling joist sizes and spacing in compliance with Table R802.4.
Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.

ELEVATIONS:

1. Provide an attic space ventilation calculation and specify size and location of all vents needed to comply, R806.2.

SECTIONS - DETAILS:

1. Provide a header schedule or show sizes consistent with Table 502.5(1) & (2).
2. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
3. Unvented attic space may not be used with Fiber Glass Shingle roof surfaces. Show compliance with R806 by providing calculated venting or a conditioned attic space (insulation at underside of roof surface) with Tile, Metal or Built-up covering and "no vapor retarders at the ceiling".
4. Calculate the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation.
5. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing over the wall and eave area if eave vents are used, R806.3. This may be accomplished w/ baffles.
6. Note and specify a consistent roofing system, R905. Revise Detail 1/6 or 4/6.

PLUMBING PLANS:

1. Provide a plumbing design using a single code, 2006 UPC or 2006 IRC. Change the code references from IRC to UPC, or use IRC rather than UPC water fixture units.
2. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for clothes washer and dishwasher water connections, UPC 609.10. IRC P2903.5.
3. Show a gas or electric water heater with utility service.

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended).
2. Provide return air duct and register sizes, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).

ELECTRICAL PLANS:

1. Revise the electrical riser diagram showing an ampacity consistent with the Load Calculation, E3303. Note the grounding and bonding method, E3507.
2. Designate the circuit number at the location of each appliance (Water Heater), E3603.5.
3. Show overcurrent protection not exceeding the allowable conductor ampacity (circuit 2, 4), E3605.5.
4. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show a correct unshielded maximum lumen calculation.
2. Provide cut sheets for all full cut-off fixtures showing the lamp placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the correct zone and ceiling value on the plans (sheet 2 & 3), N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2008 CPIERCE1 OUT TO CUSTOMER Completed
10/15/2008 SUE REEVES REJECT SHELF Completed