Permit Number: T08CM00948
Parcel: 13312006J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00948
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the exhaust fan is to start automatically when cooking commences. Reference: Section 507.2.1.1, IMC 2006.
2. The exhaust fan is located within 10 feet of the roof edge. If the parapet is less than 42" in height, provide a guard per Section 304.10, IMC 2006.
06/05/2008 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review