Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00948
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/17/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the exhaust fan is to start automatically when cooking commences. Reference: Section 507.2.1.1, IMC 2006. 2. The exhaust fan is located within 10 feet of the roof edge. If the parapet is less than 42" in height, provide a guard per Section 304.10, IMC 2006. |
06/05/2008 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |