Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00947
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2008 GERRY KOZIOL WWM REVIEW Approved
05/09/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-09-08
Activity: T08CM00947
Address: 2502 East Allen Road
Applicant: Accord Construction

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
3. Provide construction drawings printed with black ink for review.
4. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All plan pages should reference this code.

STRUCTURAL PLANS:
5. Provide accurate cross-references to detail page.
6. Specify size of all load-bearing beams (justify 6x6 beam at carport).
7. Provide roof framing information for existing area where the new mechanical unit will be installed.

SECTIONS - DETAILS:
8. Provide positive connection for porch ledger, R801.2.

PLUMBING PLAN:
9. Fixture unit schedule required for the entire property (including existing) UPC Tables 6-5 and 7-3.

ELECTRICAL PLAN:
10. Specify circuit number for bathroom circuit. Note: Bathrooms require a separate 20-amp circuit, E3801.6.
11. Hallways of 10' or more in length require a receptacle, E3801.10.

INTERNATIONAL ENERGY CONSERVATION CODE:
12. Specify a "U" factor and solar heat gain coefficient of the windows and doors that meets or exceeds the requirements of N1102.1. The simplified prescribed energy value for climate zone 2B glazing and skylights is U=0.75, the default SHGC is 0.40.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status