Permit Number: T08CM00946
Parcel: 133090500

Address:
7901 E MABEL DR

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00946
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2008 SEPTIC APPROVAL WWM REVIEW Denied NEED DESIGN & FEE FOR SEPTIC REVIEW
04/17/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-19-08
Activity: T08CM00946
Address: 7901 E. Mabel Dr.
Applicant: Scott Isles

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL PLANS:
3. Provide braced wall panels 25' on center, Table R602.10.1.

PLUMBING PLAN:
4. Provide pressure regulator on water supply when static water pressure exceeds 80 psi, UPC 608.2.
5. Include bar sink on waste isometric.
6. Provide an accurate fixture unit schedule, UPC Table 6-4.
7. Size water supply line from meter to house according to proposed demand, 610.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
04/22/2008 SHANAE POWELL REJECT SHELF Completed