Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00930
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | PREVIOUS COMMENTS: ITEM 2. LETTERING ON ALL DRAWINGS HAS NOT BEEN CHANGED TO 1/8" MINIMUM, IT IS 3/32. NEED TO CHANGE LETTERING SIZE OR OBTAIN APPEAL FROM BUILDING OFFICIAL. APPEAL MUST BE SUBMITTED WITH PERMIT REVIEW DOCUMENTS. ITEM 3. NEED APPROVAL FROM BUILDING OFFICIAL FOR DEFFERRED SUBMITTALS. APPROVAL MUST BE SUBMITTED WITH PERMIT REVIEW DOCUMENTS. |
05/19/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | PREVIOUS COMMENTS: ITEM 11. ANSI 306.3 REFERS TO KNEE CLEARANCE 25" FROM FRONT OF SINK FOR MAXIMUM DEPTH OF THE REQUIRED 30 X 48 CLEAR SPACE. AS SHOWN ON THE FLOOR PLAN, THE DOOR SWING ALREADY ENCROACHES INTO THE REQUIRED SINK CLEAR SPACE. WHEN DRAWN PROPERLY, THE SINK CLEAR SPACE WILL BE DRAWN FURTHER INTO THE DOOR SWING. 2006 IBC, SECTION 1109.2.1.1 STATES THAT THE DOOR SWING MAY ENCROACH UPON CLEAR SPACES IF IT IS A PRIVATE TOILET. |
06/02/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |