Permit Number: T08CM00926
Parcel: 13824093E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00926
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2008 DAVE MANN FIRE REVIEW Approved
03/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006
03/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00926 3/20/08

1. Registrant now needs to indicate expiration date below seal. Effective March 8, 2008, Arizona State Board of Technical Registration.
2. Ground the telephone system per NEC 800.100. Specify the size of the grounding conductor.
3. OL-19 is indicated twice on the plans.
4. OL-7 and OL-9 have 900 and 720 VA respectively.
5. Incomplete review. Will do panels, feeders, load calcs and AFC next review.
03/20/2008 ROBERT SHERRY WATER REVIEW Approved
03/20/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL DETAILING AND CALCULATIONS FOR MECHANICAL EQUIPMENT ON ROOF
2. PROVIDE FIRE PARTITION CODE EVALUATION
3. PROVIDE SHELL BUILDING DRAWINGS
03/20/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/10/2008 CPIERCE1 WWM REVIEW Needs Review
04/10/2008 CPIERCE1 ZONING REVIEW Needs Review
04/10/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review