| 03/20/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/20/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006 |
| 03/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00926 3/20/08 1. Registrant now needs to indicate expiration date below seal. Effective March 8, 2008, Arizona State Board of Technical Registration. 2. Ground the telephone system per NEC 800.100. Specify the size of the grounding conductor. 3. OL-19 is indicated twice on the plans. 4. OL-7 and OL-9 have 900 and 720 VA respectively. 5. Incomplete review. Will do panels, feeders, load calcs and AFC next review. |
| 03/20/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/20/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE STRUCTURAL DETAILING AND CALCULATIONS FOR MECHANICAL EQUIPMENT ON ROOF 2. PROVIDE FIRE PARTITION CODE EVALUATION 3. PROVIDE SHELL BUILDING DRAWINGS |
| 03/20/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/20/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/10/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 04/10/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 04/10/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |