Permit Number: T08CM00909
Parcel: 112062340

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00909
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2008 MARTIN BROWN FIRE REVIEW Approved
03/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
03/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/19/2008 ROBERT SHERRY WATER REVIEW Approved
03/19/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/19/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/21/2008 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
03/21/2008 GERRY KOZIOL WWM REVIEW Approved
03/21/2008 CPIERCE1 ZONING REVIEW Needs Review
03/21/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review