Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00909
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/19/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 03/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/19/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/19/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/19/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/21/2008 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 03/21/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/21/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 03/21/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |