Permit Number: T08CM00906
Parcel: 136384150

Address:
3901 S KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM00906
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM00906
3901 S Kolb Rd.
Site Plan

TRANSMITTAL DATE: 07/14/08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. The following comments have not been addressed. DS 2-02.2.1.20 Provide the recordation information (docket and page) for the new 15' water easement on the site plan.

The indicated private access easement does not appear to correctly define the areas needed for access to both properties. This easement will need to be redefined or could be abandoned (provide recordation docket and page for abandonment on the site plan).

A perpetual vehicular, pedestrian and parking cross access agreement could be provided (provide recordation docket and page on the site plan). Provide a copy of the agreement with next submittal.

2. These comments are minor in nature and can be reviewed over the counter by setting an appointment with me.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08Cm00906-3.doc
09/10/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
09/15/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A 6' wall is required to screen loading zones from Kolb Rd. per LUC Table 3.7.2-I.

2. Required landscape plans shall include a summary of plants required for mitigation and show their site location on the landscape plans DS 2-15.3.4.B.2. Show the disposition of, TOS, as shown in the NPPO summary.

3. Include the location if applicable of a temporary holding nursery to be used for salvaged plants.
09/16/2008 ANDREW CONNOR NPPO REVIEW Denied Required landscape plans shall include a summary of plants required for mitigation and show their site location on the landscape plans DS 2-15.3.4.B.2. Show the disposition of, TOS, as shown in the NPPO summary.

Include the location if applicable of a temporary holding nursery to be used for salvaged plants.
09/30/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Mardonio Talavera DATE: September 30, 2008
Talavera Engineering and Construction
2455 E. Speedway Blvd.
Tucson, Arizona 85719

SUBJECT: Kolb Road Assist. Liv., 3901 S. Kolb Road
Site plan T08CM00906 (Third Review)
T14S, R15E, Section 32

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. The Det./Ret. basin has slopes that are greater than 4:1 and is deeper than 2 feet. Therefore security barriers will be required at the top of the basin……..per Stormwater Detention/Retention Manual Chapter 3.6.2.

Drainage Report:
1. The DR has been accepted by engineering.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
3901 S. Kolb Rd._Site 3
10/02/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.