Permit Number: T08CM00904
Parcel: 12217365A

Review Status: Completed

Review Details: SITE

Permit Number - T08CM00904
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2008 SREEVES1 ADA REVIEW Passed NOT A COT PROJECT
04/23/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Apartments for TMM and Angle Campus
T08CM00904
Site Plan (1st Review)

TRANSMITTAL DATE: April 23, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the area of the new apartment building and parking.

2. D.S. 2-02.2.1.A.3 Provide the property address on the site plan.

3. D.S. 2-02.2.1.A.5 Provide the lot line bearings on the plan.

4. D.S. 2-02.2.1.A.6 Provide the height and overall dimension for the proposed building on the plan.

5. D.S. 2-02.2.1.A.7 The zoning setbacks shown for the proposed building to the streets are shown incorrectly. Per LUC Section 3.2.6.5.B the setback from Country Club Road should be measured from the back of future curb and for Addams Street from the back of existing curb. Zoning acknowledges that it appears the building will meet setbacks.

6. D.S. 2-02.2.1.A.8 Per ICC/ANIS A117.1-2003 Section 502.4.1 the access aisle for the proposed angled handicapped vehicle parking space should be located on the passenger side of the parking space.

7. D.S. 2-02.2.1.A.8 On the standard vehicle parking space detail the angle shown calls for "45 1/8 degrees, please clarify. Also per LUC 3.3.7.2 and D.S. 3-05.6.0 Table 1 provide the Curb Length dimension on the detail.

8. D.S. 2-02.2.1.A.8 Provide a wheel stop for the proposed angled handicapped vehicle parking space.

9. D.S. 2-02.2.1.A.12 There is a proposed one-way sign shown in the middle of the sidewalk on the east side of the proposed entrance parking area access lane (PAAL). Relocate this sign.

10. D.S. 2-02.2.1.A.12 It is not clear how the required continuous pedestrian circulation/accessible route connects to the existing pedestrian circulation. Per D.S. 2-08.3.1 is required to connect to all buildings on site. It appears that there is a three (3) foot sidewalk proposed along the north side of the proposed building but it is not clear how the sidewalk along the south side of the proposed building. Per D.S. 2-08.5.1.A all sidewalks on site must be four (4) foot wide.

11. D.S. 2-02.2.1.A.13 If applicable provide the location, type, size and height of existing and proposed freestanding signage and billboards.

12. D.S. 2-02.2.1.A.20 If applicable show all easements of record graphically on the plan together with recording docket and page reference.

13. D.S. 2-02.2.1.A.25 If applicable provide existing and proposed freestanding lighting layout and type. Provide a detail; list the height of pole and type of lighting.

14. D.S. 2-02.2.1.A.31 Please provide the existing and proposed use on the plan.

15. D.S. 2-02.2.1.A.32 Show the location of the refuse container for the proposed building on the plan. If a roll off is planned show where the storage and pick-up area will be located.

16. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t08cm00904

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
04/23/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 24 APRIL 2008
T08CM00904/TMM AND THE ANGEL CAMPUS
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
2006 IBC/ICC 117.1

DENIED: SEE COMMENTS BELOW

I. SHEET CVR-1:
A. DENOTE GOVERNING ACCESSIBILITY CODE; 2006 IBC/ICC 117.1 FOR PRIVATE PROPERTY
B. DENOTE RIGHT OF WAY ACCESSIBILITY STANDARDS; COT DOT STANDARDS FOR CURB RAMPS AT DRIVE WAYS.
II. SHEET SD-1:
A. PROVIDE AND IDENTIFY ACCESSIBLE ROUTE THROUGHOUT SITE TO ALL BUILDING ENTRANCES AND EXITS AND PARKING FACILITIES AND TO NEAREST PUBLIC TRANSPORTATION POINT AS PER ICC 117.1, SECTION 402
1. SHOW LOCATION OF NEAREST PUBLIC TRANSPORTATION DROP OFF POINT.
2. SHOW R.O.W. CONNECTION TO ACCESSIBLE ROUTE.
3. CLEARLY SHOW THE EXISTING ADAMS STREET R.O.W. CONCRETE WALK WAY.
B. SHOW CURB RAMPS AT ADAMS STREET DRIVE ENTRANCE IN COMPLIANCE WITH COT DOT STANDARD DETAIL 207.
C. ACCESSIBLE PARKING:
1. PROVIDE ONE VAN ACCESSIBLE PARKING SPACE AS PER 2006 IBC, SECTION 1106; ICC 117.1, SECTION 503. PROVIDE LARGE SCALE DETAILS SHOWING SIZE OF SPACE AND ISLE, SIGNAGE, ACCESSIBLE ROUTE AND GRADE SLOPES.
2. SURFACE SLOPES FOR ALL ACCESSIBLE PARKING AREAS TO BE NO GREATER THAN 1:48, ICC 117.1, SECTION 502.5. PROVIDE SPOT GRADES REFLECTING COMPLIANCE.
3. ALL ACCESSIBLE PARKING SPACES, PRIVATE PROPERTY SIDE WALK RAMPS AND CURB RAMPS AND RAISED MARKED CROSSINGS TO MEET 2006 IBC/ICC 117.1 ACCESSIBLE STANDARDS, SECTION 406. PROVIDE LARGE SCALE DETAILS OF EACH DIFFERENT TYPE SHOWING SIZE OF SPACE AND ISLE, SIGNAGE, ACCESSIBLE ROUTE AND GRADE SLOPES. PROVIDE DETECTABLE WARNINGS AS PER SECTION 406.2
SHOW ALL DETAILS SPECIFIC TO SITE DEVELOPMENT PLAN LAYOUT, NOT "A" TYPICAL PLAN LAYOUTS.
4. SHOW LOCATIONS OF ALL ACCESSIBLE PARKING SIGNS ON THE SITE DEVELOPMENT PLAN.
5. "ACCESSIBLE ROUTE" NOTE WITH AN ARROW IS POINTING TO A VEHICLE AISLE. CORRECT NOMENCLATURE.
D. ACCESSIBLE DETAILS:
1. BOTTOM OF LARGER SIGN TO BE 7'-0" ABOVE FINISHED GRADE AS PER COT DOT STANDARDS.
E. INSURE COMPLIANCE WITH ICC 117.1, SECTION 307.4, VERTICAL CLEARANCE AT BOTH STAIRS.
F. ACCESSIBLE BUILDING EGRESS NEEDS TO BE EVALUATED FOR COMPLIANCE WITH IBC SECTIONS 1007, 1015, 1019, AND 1105.
III. SHEET C2:
A. SHOW NORTH PARKING LOT CHANGES AS PER SITE DEVELOPMENT PLAN LAYOUT. SHOW ALL RAMPS AND SPOT GRADES SHOWING SLOPE COMPLIANCE.
B. ACCESSIBLE ROUTE/WALK WAYS ARE NOT SAME AS SITE DEVELOPMENT PLAN. REVISE ACCORDINGLY AND PROVIDE SPOT GRADES TO SHOW SLOPE COMPLIANCE.
C. PROVIDE REQUIRED ADDITIONAL ACCESSIBLE ROUTE SPOT ELEVATIONS TO ADEQUATE EVALUATE SLOPE COMPLIANCE.
D. PROVIDE SPOT GRADES AT ALL ACCESSIBLE PARKING SPACES TO SHOW SLOPE COMPLIANCE; 2% MAX.

END OF REVIEW
04/29/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border or fraction thereof per LUC 3.7.2.4. With a street landscape border length of 210 feet a total of 7 canopy trees are required along the Adams Street landscape border.

2. The flowering plum (Prunus) tree is not found on the approved drought-tolerant plant list and may not always grow large enough to be a good parking lot shade canopy tree. It is recommended that the plant schedule be revised to propose a different canopy tree.

3. A detention basin located within the Adams Street landcsape border is labeled on the landscape plan but no details or cross sections are provided for the basins. Revise the landscape plan to include slope ratios for retention and detention basins. Basin slopes in most instances are required to have slopes no steeper than 4:1 where depths exceed three feet; 3:1 for unprotected slopes and 2: 1 for protected slopes for depths less than three feet.
DS 10-01.4

4. Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Landscape borders proposed in right-of-way areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements.
LUC 3.7.2.4.A.3

4. Walls, fences, or other screening must be placed behind the landscape border. Walls constructed in a single continuous line shall extend into a street landscape border no more than the actual width of the wall. Where a wall incorporates offsets or similar design features, a screen may extend a maximum of three (3) feet into the street landscape border. LUC 3.7.3.2.C.3

5. Provide a copy of the last approved landscape plan.

6. The area between the right-of-way line and sidewalk and the area between the sidewalk and the curb, if not covered with vegetation, shall be covered with an appropriate inorganic ground cover, such as decomposed granite. Revise the plans to clarify compliance. LUC 3.7.2.4.A.4

7. Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site
storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of
all runoff, from individual catch basins around single trees to basins accepting flow from an entire
vehicular use area or roof area. LUC 3.7.4.3.B

8. Based on the expansion of vehicle use area given, this project is considered a greater than 50 percent expansion. There is 16,555 square feet of vehicle use area shown on the last approved plan provided, and 27,350 square feet shown on sheet SD-1 for this project, which equals an expansion of 60.5 percent. Revise plans to show how landscaping, screening and all other site elements meet land use code requirements for the entire site.
Further comments may apply.
04/30/2008 PETER MCLAUGHLIN NPPO REVIEW Denied Submit Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
05/28/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: May 28, 2008
SUBJECT: 3127 E Adams
TO: George Holguin - ADC West
LOCATION: 3127 E Adams, T14S, R14E, Section 4, Ward 6
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM00904 (First Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.


Please include a response letter to the comments along with the corrected copies of the site plan.

Site Plan:


1. As per the Federal ADA requirements, verify that all wheel chair ramps shall be constructed in accordance with COT SD 207.
2. Provide North arrow and scale per D.S. 2-02.2.1.1.
3. Please provide project address per D.S. 2-02.2.1.3.
4. Modify location map to meet the minimum requirements. Show the porperty approximately centered within the one (1) square mile area; drawn map at a minimum scale of 3" = 1mile and provide section, township, range and section corners.
5. Verify that all lettering and dimensions are equivalent to twelve (0.12) point or greater in size.
6. Verify that all lot dimensions and bearings are clearly indicated on site plan per D.S. 2-02.2.1.5
7. Provide all existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use per D.S. 2-02.2.1.6.
8. Label Country Club as an Arterial Road and label Adams Street and Lee Street as a local street.
9. Label existing and future sight visibility triangles and provide dimensions on site plan per D.S. 2-02.2.1.10.
10. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
11. Show and label the existing driveways adjacent to the site and verify the 12-foot minimum width. Refer to Tucson Code (TC) Chapter 25-39 for curb cut and driveway requirements.
12. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12. Specifially label PAAL.
13. South of the building there is a symbol that is not called out. They appear to be truncated domes. Please calify in response comment. Cerify that all handicap access ramps at crosswalks or at the transition of a pedestrian circulation area to a vehicular use area have required detectable warning devices (truncated domes) per ANSI Standards A117.1-2003 Section 406.13.
14. DS Sec.2-02.2.1.A.12: Revise the site plan to show the required pedestrian circulation path that is required from the proposed buildings to the required pedestrian circulation path located along Adams Street.
15. Provide drainage patterns and finished grades per D.S. 2-02.2.1.16.
16. Verify that depressed curbing is provided so that onsite drainage is able to enter landscaped areas. Provide detail for depressed curbing.
17. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
18. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Adams Street and Lee Street.
19. DS Sec.2-02.2.1.A.19: Label the 11-foot future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW.
20. Verify that sll easement of record have been graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
21. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the site plan.
22. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
23. Provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
24. Show site plan number in the lower right hand corner of each sheet pertaining to the site plan per D.S. 2-02.2.1.29.
25. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
26. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the Grade Break at the Driveway, if applicable.
27. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
28. All symbols on plans need to be indicated in legend. Indicate all symbols in legend.
29. Provide area of disturbance. (SWPPP).
30. Provide phase(s) on site plan.
31. For proposed retention/detention basin provide the following:
a. Provide at least one (1) typical cross-section.
b. Provide dimensions on plan view of site plan.
c. Provide WSE on the site plan.
d. Indicate weir outlet and inlet on the site plan.
e. Provide spot elevations around the top of the basin and within the basin. Clearly show that minimum 1% slope if established within basin.
f. Provide bleed pipe for basin and identify on site plan.
g. Indicate point of access.
32. Additional comments may be forthcoming.

Drainage Report:

1. Provide hydrologic data sheet and boundary watershed
2. In the Drainage Report discuss how the basin will be maintained. Specify whether there will be vehicular access and describe the erosion protection at outlets.
3. Further explain offsite flows coming onto the site from the south side and explain how the water is
conveyed through the site.
4. Provide hydrologic data sheet and boundary watershed delineation of offsite watershed that 4 cfs
was derived from, to assure site addresses existing flows entering the site.
5. Specify for all disturbed areas they proposed perminant erosion control to be placed (i.e. gravel or
revegetation).
6. Provide on drainage exhibit the Basin Volume, Inlet Q100, Outlet Q 100, Basin bottom elevation,
etc.
7. Additional comments may be forthcoming.


If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2008 CPIERCE1 OUT TO CUSTOMER Completed