Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise drawing to clearly show the extent of the new work. remove keynotes for the previous project.
03/27/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00859 3/27/08

1. FC-2, WITH 4.9A, does not appear to have proper Ground Fault and Short Circuit protection. Reference NEC 430.52.
2. Not known what P-1 is. Please corrdinate with Mechanical.
3. It appears that Phase A on Panel L2P is overloaded when continuous load and largest motor are factored in.