Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM00859
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise drawing to clearly show the extent of the new work. remove keynotes for the previous project. |
| 03/27/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00859 3/27/08 1. FC-2, WITH 4.9A, does not appear to have proper Ground Fault and Short Circuit protection. Reference NEC 430.52. 2. Not known what P-1 is. Please corrdinate with Mechanical. 3. It appears that Phase A on Panel L2P is overloaded when continuous load and largest motor are factored in. |