Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM00815
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/21/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/21/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/24/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/05/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/06/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |