Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00814
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/19/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/19/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00814 3/19/08 1. Circuiting of exit light on receptacle run violates NEC 700.12 (F). 2. Receptacle loads shall be counted at a minimum of 180VA per duplex outlet. Reference NEC 220.14 (I). 3. Minimum font size 1/8". 4. Reference Note 2, provide single line diagram on plans before permitting, not contractor. 5. Reference Note 2, it is not known why IECC calculaions would be needed for this project. 6. Branch circuit loading does not appear to be correct. Equipment protected by 15A, 20A, 30A, and 50A breakers would not all have identical electrical loads. 7. Arizona State Board of Technical Registration Statutes 32-143 Exceptions, states: A registrant under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project. This exception does not apply to public works projects. Based upon the plans and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer. |
03/19/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/19/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. WOMEN'S RESTROOM CAN NOT BE ACCESSIBLE THROUGH A PRIVATE OFFICE. 2. MEN'S RESTROOM CAN NOT BE ACCESSIBLE THROUGH STORAGE AREA. 3. VERTICAL GRAB BAR IN RESTROOMS REQUIRED. |
03/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006. 2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 3. Clarify how the water closet in the women's restroom is to be relocated. |
05/12/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/12/2008 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
05/12/2008 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
05/12/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |