Permit Number: T08CM00814
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00814
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2008 MARTIN BROWN FIRE REVIEW Approved
03/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00814 3/19/08

1. Circuiting of exit light on receptacle run violates NEC 700.12 (F).
2. Receptacle loads shall be counted at a minimum of 180VA per duplex outlet. Reference NEC 220.14 (I).
3. Minimum font size 1/8".
4. Reference Note 2, provide single line diagram on plans before permitting, not contractor.
5. Reference Note 2, it is not known why IECC calculaions would be needed for this project.
6. Branch circuit loading does not appear to be correct. Equipment protected by 15A, 20A, 30A, and 50A breakers would not all have identical electrical loads.
7. Arizona State Board of Technical Registration Statutes 32-143 Exceptions, states:
A registrant under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project. This exception does not apply to public works projects.

Based upon the plans and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer.
03/19/2008 ROBERT SHERRY WATER REVIEW Approved
03/19/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. WOMEN'S RESTROOM CAN NOT BE ACCESSIBLE THROUGH A PRIVATE OFFICE.
2. MEN'S RESTROOM CAN NOT BE ACCESSIBLE THROUGH STORAGE AREA.
3. VERTICAL GRAB BAR IN RESTROOMS REQUIRED.
03/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. Clarify how the water closet in the women's restroom is to be relocated.
05/12/2008 GERRY KOZIOL WWM REVIEW Approved
05/12/2008 CAGUILA1 ZONING REVIEW Needs Review
05/12/2008 CAGUILA1 ENGINEERING REVIEW Needs Review
05/12/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review