Permit Number: T08CM00804
Parcel: 10707025A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM00804
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2008 DAVE MANN FIRE REVIEW Denied The hydrant shown does not appear to be from Tucson Water. Please identify the hydrant and provide approved water plan.
06/02/2008 HEATHER THRALL ZONING REVIEW Approved
06/03/2008 ANDREW CONNOR NPPO REVIEW Approved Exception
06/03/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Indicate the location & height of screening element on the landscape plan per DS 2-07.2.2.3.a.

2. Storm water detention/retention basins shall be landscaped to enhance the natural configuration of the basin. Plants located in the bottom one-third (1/3) of the detention/retention basin must be adaptable to periods of submersion. Design criteria are set forth in Development Standard 10-01.0. Include basin landscaping.
06/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/24/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Daniel Brock III DATE: June 24, 2008
145 E. University Dr.
Mesa, Arizona 85201

SUBJECT: Phoenex Fuel, 941 W. Fairview Business Park Pl.
Site plan T08CM00804 (Second Review)
T13S, R13E, Section 35

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP. A review will not be done without a response letter to the comments.
2. It appears a great majority of the comments were not addressedon the SP. Address comments as applicable prior to the next submittal. A review fee of $75.00 per hour will be charged if there was not a genuine effort to satisfy all comments.
3. Edit all notes containing reference to Pima County standards and replace with the applicable notes. Per previous comment.
4. Please provide property description per D.S. 2-02.2.1.3. A new legal description is required for the new lot line configurations.
5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The ends of the SVT triangles are supposed to be drawn at the edge of pavement or the face of curb. Per previous comment.
6. The max. width of any driveway is 30.00' per City of Tucson code Chapter 25-39. Per previous comment.
7. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
8. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP. Per previous comment.
9. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. Per previous comment.
10. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Call out which datum is being used. Per previous comment.
11. Show Site plan number (T08CM00804) on all sheets per D.S. 2-02.2.1.29. Per previous comment.
12. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. It appears that the refuse enclosure does not meet minimum requirements. The Site plan and Grading plan do not match each other for the refuse enclosure. Revise as necessary. Per previous comment.
13. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
14. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
15. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
16. A flood use permit will be required at the grading plan stage.

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS. A review will not be done without a detailed response letter describing and/or explaining the changes made to the plan.
2. It appears a great majority of the comments were not addressed to the DS. Address comments as applicable prior to the next submittal. A review fee of $75.00 per hour will be charged if there was not a genuine effort to satisfy all comments.
3. Where the drainage facilities built as the previous grading plan indicates?
4. A flood use permit will be required at the grading plan stage.
5. Show the project address or administration address on the cover sheet of the DS.
6. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/941 W. Fairview Business Park Pl. Site 2

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
09/18/2008 SUE REEVES REJECT SHELF Completed