Permit Number: T08CM00804
Parcel: 10707025A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00804
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2008 DAVE MANN FIRE REVIEW Denied A separate permit for the installation of fuel tanks is required through the Fire Department. We will need three copies of the tank installation details, all relevant cut sheets for the materials, and a permit application.

Sheet A-1 the hydrant shown as existing is not shown on Tucson Water maps.

Sheet F2 The vapor recover plans show the VR line running to the red diesel, not the unleaded. See IFC 3404.2.7.3.5.3.

Sheet E2 The emergency shut off is less than 20" from the dispenser on drive side. IFC 2203.3.
06/02/2008 HEATHER THRALL ZONING REVIEW Denied When the site plan has been approved by all divisions, and the building plans approved by structural - the building plans can be brought through the zoning review counter for continued review.
06/06/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide for bonding of the metal building according to the requirements of NEC 250.104 (C).
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
3. Put compact fluorescent fixtures on the Luminaire Schedule, and add the exterior on to the compliance calculations for outdoor lighting.
4. Add a note on the plans: "Special Inspection required for exterior lighting fixtures per Tucson Lighting Code Section 16."
5. Provide an electrical circuit(s) for the CCTV.
6. Provide a disconnecting means for the fuel pumps.
7. Please remove the redundant #4 GND between the meter and the utility transformer. The fourth 4/0 conductor will convey any fault current back to the source on the line side of the service disconnecting means.
8. Please specify that the conduit for Fixtures B shall be sealed at both ends. Similar to the direction provided on Sheet E1, Keynotes 1,2, and 5.9. Provide exact specification for the type
06/23/2008 PAUL MACHADO ENGINEERING REVIEW Denied See Site plan comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
09/18/2008 SUE REEVES REJECT SHELF Completed