Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM00775
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2008 | ANY | ZONING | REVIEW | Active | |
| 03/07/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/10/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CALCULATIONS CALL OUT 4'-0" WIDE X 3'-0" DEEP GRADE BEAM (LATER CHANGED TO 5'-0" WIDE), WHILE THE DRAWINGS (SHEET S5.0, SECTION A) INDICATE A 4'-0" WIDE X 2'-0" DEEP GRADE BEAM. PLEASE CLARIFY. 2. DRAWING S5.0, SECTION A: PROVIDE STIRRUP SPACING PER CALCULATIONS. |
| 03/11/2008 | DAVE MANN | FIRE | REVIEW | Approved |