Permit Number: T08CM00768
Parcel: 13734001D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00768
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Sign and seal the envelope energy calculations.
2. Show that the building and the calculations are coordinated (i.e. R-30 insulation in the roof, R-17 continuous insulation in the walls, etc)
05/20/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/21/2008 CAGUILA1 ZONING REVIEW Needs Review
05/21/2008 CAGUILA1 WWM REVIEW Needs Review