Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00768
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE NOTE 2 OF LAST REVIEW. STILL NEED CALCULATIONS FOR NEW UNITS ON EXISTING ROOF STRUCTURE. |
05/13/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. Show that the building envelope meets the requirements of IECC 2006 or ASHRAE/IESNA 90.1-2004. Reference: Sections 501.1 and 501.2, IECC 2006, as amended by the City of Tucson |
05/13/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments (see sheet C1). Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. 2. Comment not addressed. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how an instantaneous water heater that delivers a 41degree Fahrenheit rise can guarantee a maximum delivery temperature of 110 degrees Fahrenheit to a lavatory faucet. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
05/19/2008 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
05/19/2008 | CAGUILA1 | WWM | REVIEW | Needs Review |