Permit Number: T08CM00768
Parcel: 13734001D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00768
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE NOTE 2 OF LAST REVIEW. STILL NEED CALCULATIONS FOR NEW UNITS ON EXISTING ROOF STRUCTURE.
05/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Show that the building envelope meets the requirements of IECC 2006 or ASHRAE/IESNA 90.1-2004. Reference: Sections 501.1 and 501.2, IECC 2006, as amended by the City of Tucson
05/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing
Code with Local Amendments (see sheet C1). Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Comment not addressed. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees
Fahrenheit), specify how an instantaneous water heater that delivers a 41degree Fahrenheit rise can guarantee a maximum delivery temperature of 110 degrees Fahrenheit to a lavatory faucet. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
05/19/2008 CAGUILA1 ZONING REVIEW Needs Review
05/19/2008 CAGUILA1 WWM REVIEW Needs Review