Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; FLOOR PLAN: EXIT THROUGH THE OFFICE IN THE SE CORNER OF THE BUILDING CAN NOT BE CONSIDERED AN OCCUPANT EXIT IF THE OFFICE DOOR CAN BE LOCKED (PER IBC 1014.2). MINIMUM NUMBER OF EXITS (2) STILL MEET REQUIREMENTS.
2. SHEET M1; PLAN: VERIFY ROOF TOP AC UNITS ARE CAPABLE OF BEING SUPPORTED BY EXISTING JOISTS. PROVIDE STRUCTURAL CALCULATIONS.
3. SHEET A1; PLAN: HIGH/LOW DRINKING FOUNTAIN REQUIRED PER ICC/ANSI SECTION 602, OR POINT OF USE WATER DISPENSER.
04/22/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/28/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how an instantaneous water heater that delivers a 41degree Fahrenheit rise can guarantee a maximum delivery temperature of 110 degrees Fahrenheit to a lavatory faucet. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
05/02/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Show that the building envelope meets the requirements of IECC 2006 or ASHRAE/IESNA 90.1-2004. Reference: Sections 501.1 and 501.2, IECC 2006, as amended by the City of Tucson
05/12/2008 GBONILL1 ZONING REVIEW Needs Review
05/12/2008 GBONILL1 WWM REVIEW Needs Review