Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00768
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Considering the temperature range for domestic water in Tucson, provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. See also: http://www.ci.tucson.az.us/tucsonwater/clearwater?output=allTabular |
| 04/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Show that the building envelope, mechanical systems, service water heating, and lighting meet the requirements of ASHRAE/IESNA 90.1-2004. Reference: Sections 501.1 and 501.2, IECC 2006, as amended by the City of Tucson. |
| 04/21/2008 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 04/21/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 04/21/2008 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/21/2008 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/21/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 04/21/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/21/2008 | DELMA ROBEY | REJECT SHELF | Completed |