Permit Number: T08CM00768
Parcel: 13734001D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00768
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2008 PAUL MACHADO ENGINEERING REVIEW Approved
03/10/2008 DAVE MANN FIRE REVIEW Approv-Cond
03/10/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the building envelope, mechanical systems, service water heating, and lighting meet the requirements of ASHRAE/IESNA 90.1-2004. Reference: Sections 501.1 and 501.2, IECC 2006, as amended by the City of Tucson.
03/10/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/10/2008 ROBERT SHERRY WATER REVIEW Approved
03/10/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied TABLE 2902.1 OF IBC REQUIRES ONE WATER CLOSET AND ONE LAVAOTRY PER 50 OCCUPANTS. REVISE DRAWINGS TO MEET THIS REQUIREMENT.
03/10/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the specification for P-1 to include the requirement that the faucet shall remain operable for a minimum of 10 seconds. Reference: Section 606.4, ICC/ANSI A117.1-2003.
2. Provide the minimum plumbing fixtures required for educational occupancy per Chapter 29, IBC 2006.
3. Clarify how the proposed instantaneous water heaters will work with the thermostatic mixing valve shown in detail 205/P3.
04/16/2008 CAGUILA1 WWM REVIEW Needs Review
04/16/2008 CAGUILA1 ZONING REVIEW Needs Review
04/16/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review