Permit Number: T08CM00767
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00767
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2008 STEVE SHIELDS ZONING REVIEW Approved
03/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/24/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00767 3/24/08

1. Ckt 200L-3 is used 3 times on the Power Plan.
2. Keynote 1 used twice on Single Line Diagram Notes.
3. Since published fault at Panel 200H is 11.2 kA, justify its 10K rating.
4. Show the existing location of relocated Panel 200H with respect to the electrical service. Unless it is clear that the new distance is smaller than the existing, provide fault calculations.
03/24/2008 ROBERT SHERRY WATER REVIEW Approved
03/24/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/24/2008 LOREN MAKUS ENGINEERING REVIEW Approved
03/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/24/2008 DAVE MANN FIRE REVIEW Approved
03/24/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/26/2008 GERRY KOZIOL WWM REVIEW Approved