Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00767
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/24/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/24/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00767 3/24/08 1. Ckt 200L-3 is used 3 times on the Power Plan. 2. Keynote 1 used twice on Single Line Diagram Notes. 3. Since published fault at Panel 200H is 11.2 kA, justify its 10K rating. 4. Show the existing location of relocated Panel 200H with respect to the electrical service. Unless it is clear that the new distance is smaller than the existing, provide fault calculations. |
| 03/24/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/24/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/24/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/24/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/24/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/24/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/26/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |