Permit Number: T08CM00764
Parcel: 10603014A

Address:
104 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00764
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/21/2008 DAVE MANN FIRE REVIEW Approved
04/21/2008 ROBERT SHERRY WATER REVIEW Approved
04/22/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
04/22/2008 PAUL MACHADO ENGINEERING REVIEW Approved
04/23/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00764 4/23/08

1. Panel B is listed as 260A on the panel schedule. Confirm that this is a standard size, or clarify.
2. Document Water Heater on Plumbing plans.
3. There are (2) Panel Bs on the Single Line Diagram.
4. It appears that "Other Loads" on Panel B total 23.4 KVA, not 11.88. Final panel loading is understated.
5. There is a note by the Single Line Diagram which directs the Contractor to disconnect original loads and serve from New Panel B. It is not clear on the plans or panel schedule how this is to be done. It appears that there are 105A unaccounted-for. Please clarify.
6. Since TEP does not publish fault current data for overhead single-phase services, please add the following note to the plans: "Contractor shall provide TEP available fault current before final electrical clearance."
04/24/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review