Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00764
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Complete the water isometric (3) to show all of the pipe sizes. 2. Clarify the size of the waste for the clotheswasher; 2" on the plans but "4" ID" on the plumbing schedule. |
| 03/07/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Correct the ventilation calculations to correspond to the actual conditions and use the default population and OSA/person values. 2. Provide exhaust for restroom M. 3. Coordinate the plans and exhaust fan schedule (EF-3 and EF-4). 4. Coordinate the mounting of the condensing units with the architect. 5. Clarify how the fan coils are mounted to the roof stucture. 6. Indicate where detail 101 occurs. 7. Coordinate sheets M1 and PD1 with regard to the existing rooftop AC unit; removed on M1, remains on PD1. 8. Correct keynote #24 on sheet P1. 9. Provide a vent for the dryer in janitor's room. |
| 03/07/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2008 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 03/14/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 03/14/2008 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/14/2008 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 03/14/2008 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/14/2008 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 03/14/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |