Permit Number: T08CM00764
Parcel: 10603014A

Address:
104 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00764
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Complete the water isometric (3) to show all of the pipe sizes.
2. Clarify the size of the waste for the clotheswasher; 2" on the plans but "4" ID" on the plumbing schedule.
03/07/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Correct the ventilation calculations to correspond to the actual conditions and use the default population and OSA/person values.
2. Provide exhaust for restroom M.
3. Coordinate the plans and exhaust fan schedule (EF-3 and EF-4).
4. Coordinate the mounting of the condensing units with the architect.
5. Clarify how the fan coils are mounted to the roof stucture.
6. Indicate where detail 101 occurs.
7. Coordinate sheets M1 and PD1 with regard to the existing rooftop AC unit; removed on M1, remains on PD1.
8. Correct keynote #24 on sheet P1.
9. Provide a vent for the dryer in janitor's room.
03/07/2008 ROBERT SHERRY WATER REVIEW Approved
03/14/2008 GBONILL1 ZONING REVIEW Needs Review
03/14/2008 GBONILL1 WWM REVIEW Needs Review
03/14/2008 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/14/2008 GBONILL1 ENGINEERING REVIEW Needs Review
03/14/2008 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
03/14/2008 GBONILL1 FIRE REVIEW Needs Review
03/14/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review