Permit Number: T08CM00754
Parcel: 14111031A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00754
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
03/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference Section 106.1.1, IBC 2006.
03/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference Section 106.1.1, IBC 2006.
2. Provide the minimum plumbing facilities (i.e. a drinking fountain or a water dispenser permanently attached to a water supply) required by Table 2902.1, IBC 2006, for storage occupancy.
3. Provide a copy of the approved shell package drawings.
4. Show how the temperature of the hot water supply to the public lavatories is to be set using the specified faucet, considering the variation of water temperature throughout the year. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Note #4 of the water calculations is not allowed per Section 610.1, UPC 2006.
6. Provide a watertight pan of corrosion-resistant material under the water heater with a drain to an approved location. Reference Section 508.4, UPC 2006.
7. Provide a vacuum relief for the water heater. Reference Section 608.7, UPC 2006.
03/06/2008 ROBERT SHERRY WATER REVIEW Approved
03/06/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/06/2008 PAUL MACHADO ENGINEERING REVIEW Approved
03/11/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed On Hold - Needs Review to Verify Suite Numbers -

Impact Fee's Do Apply; Southeast District; 5,508 Square Feet of Warehouse; $11,517.23.

The Portion of Suite #180 that was built out and occupied from T06CM06428 has been subtracted from the Impact Fee's, and the Net Total of New Square Footage is for 5,508 Square Footage which will be applied for impact fee's
03/12/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t08cm00754 3/12/08
1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference Section 106.1.1, IBC 2006.
2. Egress lighting not in compliance with NEC 700.12 (F).
3. Provide service load calculations.
03/12/2008 DAVE MANN FIRE REVIEW Approved
04/01/2008 GERRY KOZIOL WWM REVIEW Approved